张惠琳, 李醒飞, 杨少波, 徐佳毅, 李洪宇, 王强. 深海自持式智能浮标双闭环模糊PID定深控制[J]. 信息与控制, 2019, 48(2): 202-208, 216. DOI: 10.13976/j.cnki.xk.2019.8270
引用本文: 张惠琳, 李醒飞, 杨少波, 徐佳毅, 李洪宇, 王强. 深海自持式智能浮标双闭环模糊PID定深控制[J]. 信息与控制, 2019, 48(2): 202-208, 216. DOI: 10.13976/j.cnki.xk.2019.8270
ZHANG Huilin, LI Xingfei, YANG Shaobo, XU Jiayi, LI Hongyu, WANG Qiang. Dual Closed-loop Fuzzy PID Depth Control for Deep-sea Self-holding Intelligent Buoy[J]. INFORMATION AND CONTROL, 2019, 48(2): 202-208, 216. DOI: 10.13976/j.cnki.xk.2019.8270
Citation: ZHANG Huilin, LI Xingfei, YANG Shaobo, XU Jiayi, LI Hongyu, WANG Qiang. Dual Closed-loop Fuzzy PID Depth Control for Deep-sea Self-holding Intelligent Buoy[J]. INFORMATION AND CONTROL, 2019, 48(2): 202-208, 216. DOI: 10.13976/j.cnki.xk.2019.8270

深海自持式智能浮标双闭环模糊PID定深控制

Dual Closed-loop Fuzzy PID Depth Control for Deep-sea Self-holding Intelligent Buoy

  • 摘要: 针对深海自持式智能浮标运动模型非线性、强耦合性的特点,提出了一种基于双闭环反馈回路的模糊比例-积分-微分(proportion-integral-derivative,PID)定深控制器.根据浮标的浮力调节机构,分析了浮标的运动过程,建立了非线性运动方程.针对外环深度反馈回路,设计了模糊控制器.基于内环速度反馈回路与模糊控制器,设计了联级模糊PID定深控制器.传统PID定深控制器超调量5.6%,最终在目标深度±30 m范围内震荡,而双闭环模糊PID定深控制器在相同的上升时间内,超调量2.0%,深度误差控制在1.0%以内.存在外界扰动的情况下,通过双闭环模糊PID定深控制器的调节,浮标仍可以稳定在目标深度内.仿真结果表明,所建立的双闭环模糊PID定深控制系统具有良好的控制效果和稳定性.

     

    Abstract: Considering the nonlinear and strong coupling characteristics of the motion model of a deep-sea self-holding intelligent buoy, we propose a fuzzy proportion-integral-derivative (PID) controller based on a dual closed-loop to control the buoy's depth. According to the buoyancy regulation system, we establish a nonlinear dynamic model based on the motion analysis of the buoy. We design a fuzzy controller for the outer deep feedback loop, and then we design a cascade fuzzy PID controller for deep-sea self-holding profile buoy according to the inner speed feedback loop and the fuzzy controller. The overshoot of the traditional PID depth controller is 5.6%, and it will eventually oscillate within a depth of ±30 meters. Compared with traditional PID depth controllers, within the same rise time, the overshoot of the fuzzy PID controller is 2.0%, and the depth error is within 1.0%. In the presence of external disturbances, the buoy can still be stabilized within the target depth by adjusting the dual closed-loop fuzzy PID depth controller. Simulation results demonstrate that the dual closed-loop fuzzy PID depth controller has better depth control ability and stability.

     

/

返回文章
返回